Talking about the design of plate heat exchanger

1, the advantages of plate heat exchangers 
The characteristics of plate heat exchangers are obvious compared with other heat exchangers: plate heat exchangers have high heat transfer coefficient, small footprint, compact structure and easy maintenance. Under the condition of equal heat transfer, the space occupied is only 1/2 to 1/3 of the shell-and-tube heat exchanger. And unlike the shell-and-tube heat exchanger, it is necessary to reserve a large space for the tube bundle to be repaired. The plate heat exchanger only needs to loosen the clamping screw, and can contact the surface of the heat exchanger plate 100% in the original space range, and is convenient to disassemble and facilitate cleaning. Small size, light weight and easy to install in a small space. Through the above analysis and comparison, it can be seen that the plate heat exchanger has many advantages over the shell-and-tube heat exchanger. In addition, the plate heat exchanger has the following advantages.
 (1)The temperature difference is small 
Because the plate heat exchanger has a high heat transfer coefficient and strong turbulence, after the flow heat transfer in the heat exchanger, the temperature of the primary and secondary hot water of the heat exchanger can be made. The difference is very small, and sometimes the temperature difference can approach 1 ° C ~ 3 ° C. This can greatly increase the thermal efficiency and improve the economics of the heat exchange equipment.  
 (2) Small heat loss 
Because the edge of the plate and the surrounding gasket are exposed to the atmosphere, the heat loss is small, generally about 1%, no need to take insulation measures. In the case of the same heat exchange area, the heat exchange loss of the plate heat exchanger is only 1/5 of the shell-and-tube heat exchanger, and the weight is less than half of the shell-and-tube type.  
 (3) Adaptability 
On the one hand, when assembling the heat exchanger, it is convenient to increase or decrease the heat transfer plate according to the output and process requirements, and the plates can be rearranged and the process combination can be re-selected. On the other hand, the adaptability is also manifested in its use. Plate heat exchangers are widely used. At present, they are widely used in various engineering fields such as chemical industry, machinery, cement, petroleum, electric power, hot water heating, etc. In the process of heating, cooling, evaporation, condensation, waste heat recovery, etc., the purpose of application is achieved by performing heat exchange between the mediums in the plate heat exchanger.  
 (4)Flexible operation, easy maintenance 
 The heat transfer plate and the movable compression plate are hung on the beam of the machine. There is a rolling device above the pressure plate, which can easily open the device, clean it, and take out a plate. Check or replace the gasket.  
By comparing the shell-and-plate heat exchanger, the following conclusions can be drawn: the heat exchanger of the plate heat exchanger has high heat transfer efficiency, small volume, light weight and easy disassembly and assembly, when cooling When the water quality is good, it is a relatively good heat exchanger equipment. Combined with the specific conditions of the heat exchange station of the district, the plate heat exchanger is suitable as the heat exchange equipment of the heat exchange station of the district.  
2. Types of plate heat exchangers 
 Spiral plate heat exchanger 
Advantages: The spiral plate heat exchanger is compact in structure and provides a large heat transfer surface per unit volume. The fluid allows a higher flow rate in the spiral plate, and the fluid flows in the spiral direction, and the stagnant layer is thin, so the heat transfer coefficient is large and the heat transfer efficiency is high. In addition, due to the large flow rate, dirt is not easily retained.  
Disadvantages: spiral plate heat exchangers require high welding quality and difficult maintenance. Heavy weight, poor rigidity, special care should be taken when transporting and installing spiral plate heat exchangers.  
 Plate heat exchanger 
Flat heat exchanger is a new type of high efficiency heat exchanger assembled from a series of metal sheets with a certain corrugated shape. A thin rectangular channel is formed between the various sheets, and heat exchange is performed through the half sheets. Compared with the conventional shell-and-tube heat exchanger, the heat transfer coefficient is much higher under the same flow resistance and pump power consumption, and there is a tendency to replace the shell-and-tube heat exchanger within the applicable range.  
 Shelf-fin heat exchanger 
consists of a bundle of heat exchanger plates enclosed in a header tank with inlet and outlet for cold and hot fluids. The bundle of plates is alternately laminated by flat plates and corrugated fins and brazed. The cold and hot fluids flow through the sides of the plate to exchange heat, and the fins increase the heat transfer area, which promotes the turbulence of the fluid and enhances the equipment. The plate-fin heat exchanger has a very compact structure, good heat transfer effect, and a pressure of up to 15 MPa. However, its manufacturing process is complicated, the flow path is small, and the internal leakage is not easy to repair, so it is limited to clean non-corrosive fluids, such as heat exchangers for air separation.  
3, general principles of plate heat exchanger design 
 Select the corrugated pattern of the board 
 The corrugated pattern of the plate is mainly herringbone corrugated and horizontal straight corrugated. The pressure bearing capacity of the herringbone corrugated sheet can be higher than 1.0 MPa, and the pressure bearing capacity of the horizontal flat corrugated sheet is generally about 1.0 MPa; the heat transfer coefficient and fluid resistance of the herringbone corrugated sheet are higher than the horizontal straight corrugation. Plate. Select the corrugated pattern of the plate, mainly considering the working pressure of the plate heat exchanger, the pressure drop of the fluid and the heat transfer coefficient. If the working pressure is above 1.6MPa, there is no choice to use herringbone corrugated sheets; if the working pressure is not high and the resistance is required to be reduced, it is better to use horizontal flat corrugated sheets; if it is limited by the installation position A high heat exchange efficiency is required to reduce the heat exchanger footprint, and the resistance drop can be unrestricted, and a herringbone corrugated sheet should be used. The plate type or corrugated type should also be determined according to the actual needs of the heat exchange occasion. For the case where the allowable pressure drop is large, the plate type with low resistance should be selected, and the plate with large resistance should be selected.  
 Selection of board area
If the area of ??the board is too small, the number of plates of the plate heat exchanger is large, and even if the floor space is increased, the number of passes increases (resulting in increased resistance); And the resistance drop is reduced, but it is difficult to ensure the necessary flow rate between the plates. It is not advisable to select a plate with too small a single plate area, so as to avoid too many plates, the flow velocity between the plates is too small, and the heat transfer coefficient is too low. This problem should be paid attention to for a large heat exchange station.  
 Selection of flow rate
The flow rate of the fluid between the plates affects the heat transfer performance and the pressure drop of the fluid. The high flow rate is high, but the heat transfer coefficient is also increased; otherwise, the opposite is true. Generally, the average flow rate between plates is 0.2-0.8 m/s. When the flow rate is lower than 0.2 m/s, the fluid will not reach the turbulent state and a large dead zone will be formed. If the flow rate is too high, the resistance drop will increase sharply. In the specific design, a flow rate can be determined first to calculate whether the resistance drop is within a given range; or the initial value of the flow rate can be obtained by a given pressure drop.
 Selection of process
 The process refers to a set of parallel flow channels in the same flow direction of a medium in a plate heat exchanger, and the flow channel refers to the medium flow in the plate heat exchanger, adjacent to two plates aisle. In general, several flow channels are connected in parallel or in series to form different combinations of cold and heat medium channels. For a plate heat exchanger with a generally symmetrical flow path, when the volume flow of the two fluids is roughly equivalent, it should be arranged in an equal process as much as possible. If the flow rates on both sides are very different, the side with the small flow rate can be arranged in multiple steps. In addition, when a medium temperature rise or temperature drop is large, a multi-pass arrangement can also be adopted. The phase change side of the phase change plate heat exchanger is generally one-way. Multi-pass heat exchangers, unless otherwise required, generally the same number of runners should be used for the same fluid in each pass.  
The problem of uniform fluid flow distribution is also reflected in the process combination method. Under the given total allowable pressure drop, the multi-pass arrangement makes the corresponding allowable pressure drop of each pass smaller, forcing the flow rate. Lower, which is not good for heat transfer. In addition, the multi-pass arrangement of the out-of-range is one of the important reasons for the reduction of the average heat transfer temperature difference and should be avoided as much as possible.  
 Selection of flow
When there is no phase change heat, the countercurrent has a large average heat transfer temperature difference. In the engineering design of general heat exchangers, the fluid is arranged to be countercurrent. For plate heat exchangers, to do this, the sides must be equal. If the arrangement is not equal, the forward and reverse flows will alternate. At this time, the average heat transfer temperature difference will be significantly less than the pure reverse flow.  
 Pressure drop requirements 
In the design and selection of plate heat exchangers, there is a general requirement for pressure drop, so it should be checked. If the check pressure drop exceeds the allowable pressure drop, the design selection calculation must be repeated to know that the process requirements are met. The general manufacturer gives the pressure drop calculation formula in the sample. From the technical and economic point of view, the pressure drop of the water-heat exchanger should not exceed 0.06 MPa.
2019/05/10 19:21:32 3069 Click

许正宇:明年香港重点发展黄金市场 深化与沪深合作|香港 合肥海关查获限制出境文物木雕1件 宪法宣传周 | 《关于加强资本市场中小投资者保护的若干意见》政策速读 中国拟立托育服务法 禁止托育人员实施侵害婴幼儿身心健康的行为 日本防卫大臣小泉进次郎赴长崎视察部队 主张加强西南防卫 万台下线验证“科技豪华”路径,尊界S800重构百万级超豪华市场 华为发布鸿蒙智家全新艺术面板|华为 标准股份最新筹码趋于集中|标准股份 24件全球艺术小样亮相上博东馆 邀市民共塑城市文化记忆 华东政法大学李文莉:上海推动自贸离岸债发展,有利于推进人民币国际化进程 中国海上最大油田年产油气突破4000万吨 创造价值超50亿,对话百度秒哒:AI Coding是行业现在最有价值的一桶金|AI 爱心人寿潘华刚:生态构建中保险要扮演好自己该扮的角色 女排超级联赛:北京女排3:2逆转战胜山东女排 如何解决人民币流动性不足问题?连平:构建离岸人民币资产池,推动离岸基准收益曲线完善 航运港口板块短线走高,海峡股份涨停|航运 国家金融监管总局原首席检查官王朝弟:金融是“人工智能+”的重要领域 从“China Travel”到“China Shopping”,中国何以“圈粉”世界? 哈萨克斯坦引入技术算法强化校园欺凌治理 北芯生命IPO状态变更为注册生效|IPO 高峰:解析智能金融双轨架构与治理路径,提出数据、技术、安全三维协同破解大模型“幻觉”难题 美国最新报告:NVIDIA AI芯片将领先华为17倍!|华为|ai芯片|NVIDIA